Model |
CEP4850-EU-80-H |
AC Charge |
|
Battery Type |
Lithium-ion/Lead-acid/User Define |
Max. AC Charge Current (A) |
60 |
Charge Voltage Range (Vdc) |
40~60 |
Short Circuit Protection |
Circuit breaker and blown fuse |
Circuit Breaker Specifications (A) |
40 |
Solar Charge |
|
Max. PV Open Circuit Voltage (Vdc) |
500 |
MPPT Voltage Range (Vdc) |
120~450 |
Battery Voltage Range (Vdc) |
40~60 |
Max. PV Input Power (W) |
5,500 |
Max. PV Input Current (A) |
22 |
Max. PV Charge Current (A) |
80 |
Max. Hybrid Charge Current (A) |
80 |
Charge Short Circuit Protection |
Blown fuse |
Wiring Protection |
Inverse wiring protection |
AC Input |
|
Rated Input Voltage (Vac) |
220/230 |
Input Voltage Range (Vac) |
UPS: (170~280) ±2%; APL: (90-280)±2% |
Frequency (Hz) |
50 / 60 (Auto sensing) |
Frequency Range (Hz) |
47±0.3~55±0.3 (50) / 57±0.3~65±0.3 (60); |
Overload/short Circuit Protection |
Breaker |
Efficiency |
>95% |
Conversion Time (bypass and inverter) |
10ms (Typical value) |
AC Reverse Protection |
yes |
Max. Bypass Overload Current (A) |
40 |
AC Output |
|
Output Voltage Waveform |
Pure sine wave |
Rated Output Power(W) |
5,000(4,350/4,500/4,750/5,000) |
Power Factor |
1 |
Rated Output Voltage (Vac) |
230(200/208/220/240 settable) |
Output Voltage Error |
±5% |
Output Frequency Range (Hz) |
50±0.3 / 60±0.3 |
Max. Efficiency |
>92% |
Overload Protection |
(102% < load <125%) ±10%: report error and turn off the output after5 minutes;
(125% < load < 150%) ± 10%: report error and turn off the output after 10 seconds;
Load >150% ±10%: report error and turn offthe output after 5 seconds; |
Loaded Motor Capacity (HP) |
4 |
Output Short Circuit Protection |
Breaker |
Bypass Breaker Specifications (A) |
40 |
Rated Battery Input Voltage (Vdc) |
48 (Minimum starting voltage is 44) |
Battery Voltage Range (Vdc) |
40.0~60 ± 0.6 (Undervoltage alarm/shutdown voltage/overvoltage alarm/overvoltage recovery settable on LCD screen) |
No Load Loss (W) |
Non-energy-saving Mode: ≤50W; Energy-saving Mode: ≤25W |
General |
|
Number of parallel |
1-6 PCS |
Certification |
IEC62109, EN61000 |
Operation Temperature Range (°C) |
-15 ~ 55 |
Storage Temperature Range (°C) |
-25 ~ 60 |
Humidity Range |
5% to 95% (Conformal coating protection) |
Noise (dB) |
≤ 60 |
Heat Dissipation |
Forced air cooling, variable speed of fan |
Communication Interface |
USB/RS485/dry node control |
Size (mm) |
426Lx322Wx124D |
Weight (kg) |
10.5 |